Papua New Guinea Heptafluoropropane fire suppression system

The HFC-227ea automatic fire suppression system integrates gas fire suppression, automatic control, and fire detection into one modern intelligent automatic fire suppression device. It complies with the design specifications of DBW 5-23-1999 "HFC-227ea Clean Agent Fire Suppression System Design Specifications" and IS.14520-9 "Gas Fire Suppression Systems - Physical Properties and System Design". HFC-227ea fire extinguishing agent is highly efficient and non-toxic, harmless. The HFC-227ea fire suppression system requires a dedicated equipment room. One or more storage devices are used to protect one or more protected areas. The system uses a pipe network to deliver the extinguishing agent to the protected areas.

Product Description

Product Overview

The HFC-227ea automatic fire suppression system is a modern intelligent automatic fire suppression device integrating gas fire suppression, automatic control, and fire detection. It conforms to the design specifications of DBW 5-23-1999 "HFC-227ea Clean Gas Fire Suppression System Design Specifications" and IS.14520-9 "Gas Fire Suppression Systems - Physical Properties and System Design". HFC-227ea fire extinguishing agent has high fire extinguishing efficiency and is non-toxic and harmless. The HFC-227ea fire suppression system requires a dedicated equipment room. A system using one or more storage devices to protect one or more protected areas, using a pipe network to deliver the extinguishing agent to the protected areas.
 

Product Features

The combined distribution system consists of a set of common extinguishing agent storage devices corresponding to several sets of pipe network systems, protecting multiple protected areas. The unit independent system consists of a set of extinguishing agent storage devices corresponding to a set of pipe network systems, protecting one protected area. According to the needs, it can be divided into single-cylinder independent systems and multi-cylinder independent systems. This product features fast fire extinguishing speed, high efficiency, strong initiative, cleanliness, safety, environmental protection, and mature technology.
 

Application Scope

Suitable for protected areas with a total volume of less than 3600m³ and with permanent staff, such as generator rooms, computer rooms, switchgear rooms, archives, substations, diesel generator rooms, etc. One system protects up to 8 protected areas or spaces. Larger spaces can be protected by using multiple main pipes or layered pipelines.
 

System Operating Pressure 4.2MPa(20℃)
Maximum System Operating Pressure 5.3Mpa(50℃) 8.0Mpa (50℃)
Maximum Extinguishing Agent Filling Density 1120kg/m
Storage Container Volume 40L/70L/90L/100L/120L/150L/180L
Extinguishing Agent Discharge Time ≤10S
Driving Gas Cylinder Group Operating Pressure 6Mpa
Driving Gas Cylinder Group Volume 4L/6L/8L
Operating Voltage DC24V
Pneumatic Current ≤1.6A
Operating Temperature Range 0℃-50℃
Automatic Start Delay Time 0-30s adjustable
System Start-up Method Automatic/Manual/Mechanical Emergency