Vietnam ZSFM100-1.6G grooved diaphragm deluge valve

The ZSFM diaphragm deluge valve consists of a main valve, hydraulic alarm bell, pressure switch, manual opening valve, solenoid valve, manual reset valve, resetter, and control piping. Equipped with open sprinklers, water curtain sprinklers, water mist sprinklers, and a fire alarm control system, it can form a corresponding water spray fire extinguishing system. It features a simple structure, easy operation, reliable safety, and convenient installation and maintenance. In case of a fire, the deluge valve opens, and the system's open sprinklers spray water onto the fire source, while simultaneously automatically spraying water throughout the protected area to prevent the fire from spreading and expanding. It is suitable for buildings and sites with a high fire hazard that are prone to icing or require key protection.

Product Description

Product Overview

The ZSFM diaphragm deluge valve consists of a main valve, hydraulic alarm bell, pressure switch, manual opening valve, solenoid valve, manual reset valve, resetter, and control piping. Equipped with open sprinklers, water curtain sprinklers, water mist sprinklers, and a fire alarm control system, it can form a corresponding water spray fire extinguishing system. It features a simple structure, easy operation, reliable safety, and convenient installation and maintenance. In case of fire, the deluge valve opens, and the system's open sprinklers spray water onto the fire source, while simultaneously automatically spraying water to the entire protected area, thus preventing the spread and expansion of the fire. It is suitable for buildings and sites with high fire hazards that are prone to icing or require key protection.
 

Model Specifications ZSFM100-16GZSFM150-1.6GZSFM200-1.6G
Rated Working Pressure 1.6
Sealing Test Pressure 3.2
Strength Test Pressure 6.4
Water Supply Pressure Range 0.14-12
Alarm Port Range ≥ 0.05
Groove Standard φ114 φ165 φ219
Operating Ambient Temperature 4℃~70℃
Storage Environment Should be stored in a ventilated and dry warehouse, avoiding storage with corrosive substances. Storage temperature -10℃~+40℃
Product Standard GB5135.S-2018《Automatic Sprinkler Fire Suppression Systems Part 5: Deluge Valves》