Bangladesh ZSFC200-1.6 Dry Alarm Valve
Category:
Product Description
Product Overview
Dry alarm valves are used in dry sprinkler fire suppression systems. These systems are typically used in buildings where the ambient temperature is below 4℃. In the standby state, compressed air in the system network seals the fire pressure water on the supply side via the dry alarm valve. When a sprinkler activates, causing a drop in network air pressure to a certain value, the dry alarm valve opens, and pressurized water enters the system network through the valve to begin fire suppression.
Working Principle
The dry valve produced by our factory is characterized by its small size and light weight. It uses an eccentric valve disc. When the valve is in the standby state, the valve cover rests on two eccentric valve seats. The inner seat is the water valve seat, and the outer seat is the air valve seat. The annular space (intermediate chamber) between the two valve seats communicates with the atmosphere through the alarm pipe. There is a small amount of pre-injected water above the valve (to increase the sealing of the valve disc) and enough compressed air to close the valve disc. If any sprinkler (or multiple sprinklers) on the system side opens, causing a drop in compressed air pressure, the dry valve will open when the air pressure drops to about one-fifth of the water pressure on the supply side. Pressurized water flows into the pipeline on the system side, spraying from the open sprinkler to begin fire suppression. At the same time, water flows through the intermediate chamber to the alarm port to drive the pressure switch and the hydraulic alarm bell.
This valve has an anti-reset and external reset device. After the valve opens, it needs to be reset by externally rotating the reset handle counterclockwise (after resetting, the handle needs to be returned to the vertical position).
| Model Specifications | Rated Working Pressure | Nominal Diameter | Flange Outer Diameter (mm) | Flange Bolt Hole Center Diameter (mm) | Number and Diameter of Bolt Holes (mm) |
| ZSFC100-1.6 | 1.6MPa | DN100 | 220 | 180 | 8-φ18 |
| ZSFC150-1.6 | DN150 | 285 | 240 | 8-φ22 | |
| ZSFC200-1.6 | DN200 | 340 | 295 | 12-φ22 |
Hongan Fire Equipment Co., Ltd.
No. 101, Nantong Road, Ximei Street, Nan'an City, Quanzhou City, Fujian Province
COOKIES
Our website uses cookies and similar technologies to personalize the advertising shown to you and to help you get the best experience on our website. For more information, see our Privacy & Cookie Policy
COOKIES
Our website uses cookies and similar technologies to personalize the advertising shown to you and to help you get the best experience on our website. For more information, see our Privacy & Cookie Policy
These cookies are necessary for basic functions such as payment. Standard cookies cannot be turned off and do not store any of your information.
These cookies collect information, such as how many people are using our site or which pages are popular, to help us improve the customer experience. Turning these cookies off will mean we can't collect information to improve your experience.
These cookies enable the website to provide enhanced functionality and personalization. They may be set by us or by third-party providers whose services we have added to our pages. If you do not allow these cookies, some or all of these services may not function properly.
These cookies help us understand what you are interested in so that we can show you relevant advertising on other websites. Turning these cookies off will mean we are unable to show you any personalized advertising.